EV FirePro is a targeted suppression system for electric vehicles, designed for rapid activation and containment. It is engineered to integrate into existing water‑based parking fire suppression systems, or to operate as an additional fire protection system in spaces such as residential and commercial parking areas.
It is manufactured in Australia by EV Fire Protection, a global leader in electric vehicle fire‑response technology. EV FirePro combines patented technology, focused cooling beneath the vehicle, and perimeter side‑spray coverage. Constructed entirely from 304/316 stainless steel, it delivers maximum durability even in harsh and demanding environments. Thanks to its robust construction, the system can be installed in home garages, small and large parking facilities, as well as commercial buildings.
How it works
EV FirePro is automatically activated through a Linear Heat Detection (LHD) wire. Upon activation, it sprays water beneath the electric vehicle and provides side‑spray coverage to protect surrounding vehicles and surfaces. The Plus and Signature versions communicate with building FACP and BMS systems.
Benefits
EV FirePro significantly contributes to the protection of a parking facility’s structural elements, as its operation limits fire spread and reduces the risk of transmission to adjacent parking spaces.
Available EV FirePro Versions
EV FirePro range offers four configurations, designed for different types of installations — from residential spaces to commercial and multi‑storey parking facilities. Each version is based on the same targeted suppression technology, adapted to the needs of each specific environment.
For residential and low‑height installations.
Connection to tank & pump.
Constructed from 304 or 316 stainless steel.
For commercial and multi‑storey parking facilities.
Connection to water supply, sprinklers, hydrant, or tank/pump.
Integration with FACP & BMS.
MODEL COMPARISON TABLE
| Specification | EV FirePro Domestic | EV FirePro Plus | EV FirePro Signature | EV FirePro Demonstration Unit |
|---|---|---|---|---|
| Application | Residential & low‑height parking areas | Commercial & multi‑storey parking facilities | Premium & architecturally demanding environments | Training, exhibitions & technical evaluation |
| Activation Temperature | 68°C (standard), 88°C, 105°C | 68°C (standard), 88°C, 105°C | 68°C (standard), 88°C, 105°C | 68°C (plug‑in for repeated activation) |
| Detection Method | Linear Heat Detection (LHD) | Linear Heat Detection (LHD) | Linear Heat Detection (LHD) | Insertable LHD for demonstration |
| Water Supply Connection | Standalone tank & pump | Building water supply, sprinklers, hydrant, or tank & pump | Building water supply, sprinklers, hydrant, or tank & pump | Standard water supply or tank & pump |
| System Integration | Optional alarm connection | FACP/BMS for addressable monitoring | FACP/BMS for addressable monitoring | — |
| Construction Material | 304/316 stainless steel | 304/316 stainless steel | 304/316 stainless steel | 304/316 stainless steel |
| Corrosion Resistance | 316 for coastal/harsh environments | 316 for coastal/harsh environments | 316 for coastal/harsh environments | 316 for coastal/harsh environments |
| Mounting Method | Wall or post (when no wall is available) | Wall or post | Integrated enclosed control post | Wall or post (when no wall is available) |
| Optional Accessories | Post, tank & pump, alarm connection | Post, external weather proofing kit | — | Post, external weather proofing kit |
| Typical Installation Example | Home garages, residential complexes | Commercial buildings, parking facilities | Premium developments, mixed‑use buildings | Demonstration & training facilities |
Technical Specifications
| Dimensions | |
|---|---|
| Cover plate length | 1990 mm |
| Cover plate width | 1270 mm |
| Cover plate height (above finished floor level) | ~30 mm |
| Weights | |
| Cover plate | ~62.5 kg |
| Piping frame | ~36.5 kg |
| GRP infills (not included) | ~18.5 kg |
| Supply pipe cover plate | ~14.5 kg |
| Materials | |
| Cover plate | 3 mm stainless steel T304 |
| Piping frame | Stainless steel T304 |
| Supply pipe connection ports | Stainless steel T304 |
| Water supply hose | 50 mm high‑pressure layflat hose |
| Supply pipe cover plates | 3 mm stainless steel T304 |
| Other | 25 mm GRP (Glass‑reinforced Plastic) infills |
| Spray Nozzles (stainless steel T304) | |
| Side nozzles | 14 |
| Vertical nozzles | 7 |
| Pressure & Flow Performance (recommended) | |
| Optimal flow & pressure | 8 L/s (480 L/min) @ 750 kPa |
| Minimum flow | 4.75 L/s (285 L/min) @ 160 kPa |
| Optimal operating pressure | ~750 kPa |
| Maximum residual pressure | 1000 kPa |
| Water supply connection | Male Nb40 (1 ½” BSP thread) |
| Integrated Automatic Detection Sensors | |
| Number of temperature detection points | 20 |
| Activation temperature (adjustable) | 68°C – 185°C |
| Electrical | |
| Control panel enclosure | 300 mm W × 300 mm H × 200 mm D |
| Required power supply | 110V AC 15A – 240V AC 10A |
| Power supply unit | 110–240V AC with 24V DC output and battery charger |
| Water valve | 24V DC normally‑open solenoid valve or 24V DC motorised ball valve |
| Fire alarm relay output | 0V DC, NO/NC |
| Controls | 3‑position switch 24V DC (Auto / On / Off) |
| Indicator lights | 2 × 24V DC (green “ready”, red “fault”) |
| Auxiliary batteries (not included) | 2 × 12V DC, 2.1 Ah |
Design & Installation
EV FirePro is constructed from 304 or 316 stainless steel for seawater resistance, offering high durability against corrosion. Its low‑profile design allows smooth vehicle movement and safe pedestrian passage.
Installation can be carried out:
- on a wall,
- on a dedicated post,
- or in a custom configuration adapted to the parking environment.
Connection & Activation Methods
Water supply connection
- Building water supply
- Sprinkler system
- Fire hydrant
- Tank & pump
Activation
Automatic activation via Linear Heat Detection (LHD) cable.
EV FirePro Components & Accessories
EV FirePro is accompanied by specialized components and accessories that support the installation, protection, and operation of the system in any environment. From water‑supply cover plates to weather‑proofing kits and demonstration accessories, every element is designed for reliability, durability, and a professional finish.

Additional Water Supply Cover Plates
The water supply cover plates create a clean and protected pathway between the control column and the EV FirePro unit. The system includes two plates with a total length of 2900 mm (1500 mm fixed + 1500 mm adjustable), while additional lengths of 600 mm, 900 mm, and 1200 mm are available for installations requiring greater distance.

Post
When the EV FirePro Plus is not installed against a
wall, a post is required to support the control box and
associated fittings. The post provides a stable
mounting point for the system’s controls and ensures
a clean, professional installation finish.
Three post configurations are available:
- Internal 'surface mount' Post – designed to be securely bolted onto a concrete surface indoors.
- Surface-Mount Post – designed to be securely bolted onto a concrete surface - externally.
- In-Ground Post – extended by 300 mm for embedding and concreting directly into the ground.

External Weather Proofing KIT "Wall Mount"
The Wall Mount Weather Proofing Kit provides essential protection for the control box and components against rain, dust, and environmental exposure. Designed for systems mounted directly to a wall, this kit ensures long-term reliability and durability in external environments while maintaining a professional finish. It does not come with a post.

External Weather Proofing KIT "Post Mount"
The Post Mount Weather Proofing Kit is required when the EV FirePro is installed externally using a post configuration. It protects the control box and fittings from weather and environmental conditions, preserving system integrity and performance. Built for durability and ease of installation, the kit provides a robust and sealed solution for outdoor applications.

Αναβάθμιση Ηλεκτροκίνητης Σφαιρικής Βάνας (Motorised Ball Valve Upgrade)
Η αναβάθμιση με ηλεκτροκίνητη σφαιρική βάνα επιτρέπει τον αυτόματο έλεγχο της παροχής νερού του συστήματος EV FirePro, βελτιώνοντας την ευκολία χειρισμού και την επιχειρησιακή αξιοπιστία.
Accessories for demonstration unit

Exhibition Cover Plate
The Exhibition Cover Plate is a shortened version of the standard supply water cover plate, purposedesigned for trade shows and display environments where space is limited. Ideal for booths with a minimum depth of 3 metres, it allows the EV FirePro system to be installed neatly and functionally while maintaining a realistic presentation of the full setup within a compact exhibition layout.

LHD Wire Demo Accessory 10PK
These disposable Linear Heat Wire sticks come in packs of 10 and are designed to be plugged into the port on a Demonstration unit. Heat the end of the LHD wire with a heat gun or gas flame until it activates the EV FirePro. After use, the end of the LHD can be cut and then used again.

Replacement Linear Heat Wire
The Linear Heat Detection (LHD) Wire is a key component of the EV FirePro system, providing continuous heat sensing along its full length. Designed to automatically trigger activation when a set temperature is reached, it enables early response to thermal events beneath an EV. The LHD wire integrates with the control box or alarm interface for reliable, addressable detection in both indoor and outdoor installations. Available in 68 °C, 88 °C, and 105 °C temperature ratings. For outdoor installations in hot climates, the 105 °C wire is recommended. For moderate environments, the 88 °C wire provides optimal performance for outdoor installations.