The FoamTronic VFD is an electronic foam mixing system which accurately mixes foam concentrate and water, based on the actual firewater demand of the system. The FoamTronic is designed to cover a wide range of foam system demands.
Key Features
- UL approved foam pump
- NFPA11 compliant
- Plug and play
- System test without mixing water and foam
- No pressure loss in firewater pipe
- Compatible with all foam concentrate types
Test without mixing
To comply with the NFPA 11 standard, the operation of a foam extinguishing system must be tested annually with a live test. A large amount of foam concentrate is used for this test. This is not only harmful for the environment, but also expensive for the owner.
It is not only the purchase value of the foam concentrate, but also the additional costs as the foam must be collected, and disposed of correctly to satisfy the environmental requirements.
How it works
The accurate mixing of foam concentrate and water is achieved by the continuous monitoring of the firewater and foam concentrate flows, using electromagnetic flowmeters and a real-time adjustment of the speed of the foam pump. The accuracy and stability of the system is based on the combination of specially selected components and a unique control system with state-of-the-art logic developed specifically for FoamTronic.
The control system records all process values and alarms during operation or test which are available via a simple user friendly interface.
When compared to a traditional mechanical proportioner the user has the added benefit of being able to save money on the foam usage due to the high accuracy of controllable consistent proportioning.
System start
The system starts in one of the following ways:
- Automatically, based on minimum measured waterflow
- By an external command from the fire alarm control panel
- By a combination of the two
Self-diagnostics
The VFD Foamtronic continuously monitors the following:
- Power available
- Condition of flow meters
- Condition of frequency drive
- The PLC
System Capacity
Due to the ability to control the speed of the foam pump, the system has a very wide working range.
- Maximum water pressure: up to 16 bar
- Outlet pressure (table basis): 10–16 bar
- Foam (table basis): 3% foam mixed at 3.1%
The minimum and/or maximum flow rates can be extended using specific operating parameters. Contact us to discuss your application.