Functional Features
Sound emission can be manually adjusted on the sounder itself. At the moment of activation, groups of sounders can be synchronized. Each sounder is provided with integrated isolator circuit, that automatically takes action in case of need. Addresses can be programmed by means of the programmer or with the addressing function of Teledata smoke detection panels.
Technical Features
- Red plastic enclosure
- Provided with integrated isolator circuit
- Power supply: 18–27V
- Average power consumption: 260 μA
- Alarm consumption: 26 mA
- Initiation tripping time: 2 seconds
- IP rating: IP65
- Maximum cable cross section: 2.5 mm²
- Operating temperature: –10°C to +55°C
- Maximum humidity: 85% non‑condensing
- APPLUS approved in compliance with EN54-3 EN54-17 standards (SOUND100, SOUND101)
- APPLUS approved in compliance with EN54-3 EN54-17 and EN54-ω23 standards (SOUND110)
- APPLUS approved in compliance with EN54-3 EN54-17,EN54-23ωand UNI11744 standards (SOUND330)
- ONEPROTOCOLL communication protocol
- Isolator integrated in each device
- Manual addressing via the ONEPROGRAMMER programmer
- Reading of the voltage value at the terminals of the addressed devices
Models
SOUND 100
Addressed Siren EN54-3, EN54-17
SOUND 101
Addressed Siren with Flashing Light EN54-3, EN54-17
SOUND 110
Addressed Siren with Flashing Light EN54-3 EN54-17, EN54-23
SOUND 330
Addressed Siren with Flashing Light EN54-3 EN54-17, EN54-23, UNI11744