INTERNAL HYDRANT DN25 WITH CONSTANT FLOW

    * Required fields

    I consent to the processing of my personal data in accordance with the EU Regulation Number. 2016/679

    HYDRANT DIMENSION
    Height: 900 mm
    Width: 700 mm
    Depth: 250 mm

    RECESS DIMENSION
    Height: 920 mm
    Width: 720 mm
    Depth: 260 mm

    TECHNICAL FEATURES

    Internal hydrant with constant flow with semi-rigid hose 25 mm. Mounted on the wall (Z) or recessed (W). Nominal working pressure from 0.2 MPa to 1.2 MPa.

    Type:  Mounted on the wall

    Hose length: 30m

    Lock: Two types of locking

    Supports/bases [height x depth]: 550 x 250

    Number of supports/bases: 2 pcs.

    Type:  Mounted on the wall

    Hose length: 20m

    Lock: Two types of locking

    Supports/bases [height x depth]: 550 x 250

    Number of supports/bases: 2 pcs.

    Type:  Mounted in a recess

    Hose length: 30m

    Lock: Two types of locking

    Supports/bases [height x depth]: 550 x 235

    Number of supports/bases: 2 pcs.

    Type:  Mounted in a recess

    Hose length: 20m

    Lock: Two types of locking

    Supports/bases [height x depth]: 550 x 235

    Number of supports/bases: 2 pcs.

    Technical drawings & Instructions

    Internal hydrants with constant flow have been tested by CNBOP-PIB in Józefów, testing report no 203/BS/13.

    Test results of internal hydrant PN-EN 671-1[Z25/30]QConst with fixed setting of the output pressure (factory setting)

    Water flow rate Type of water current Supply pressure values
    Q [dm3/min] 0,5 MPa 1,0 MPa 1,5 MPa
    Compact jet 62,3 61,9 62,1
    Dispersed jet 63,8 63,6 63,5

    Related Products

    Internal hydrant DN25 with place for fire extinguisher under the hose reel – universal FIT
    Internal hydrant DN25 with place for fire extinguisher under the hose reel – MCP
    DN25 -extinguisher next to hose reel – universal_1
    INTERNAL HYDRANT DN25 WITH THERMAL INSULATION